Become one of the best substitutes in the market
详细说明
DESCRIPTION Twisted pair cable used in Konnex building management networks.
Manufactured according to European Standard EN 50090, IEC 60332-1.
TECHNICAL SPECIFICATIONS
| Conductor | Solid bare copper : 0,80±0.01 mm | ![]() |
| Insulation | PVC : 1.43±0.05 mm | |
| Identification of pairs | ||
| 1 pair | Red / Black | |
| 2 pair | White / Yellow | |
| Separator | 2 cores to the pair | |
| Pair screen | Pet foil | |
| Drain wire | Solid copper : 0.40 mm (AWG26) | |
| Shielding | Aluminum-polyester | |
| Sheath | LSZH | |
| Color | Green (other colors are available upon request) | |
| Bending radius | ≥ 7,5 x Diameter (mm) Installation | |
| Storage temperature | -25℃—+70℃ | |
| Installatiom temperature | -10℃—+50℃ | |
ELECTRICAL CHARACTERISTICS
nº Pairs.x Ф 2x2x20AWG
Conductor resistance max.73.2 Ω/km
Insulation resistance min. 100 MΩ x km
Cap.conductor to conductro @ 800kHz max. 100 nF / km
Cap. unbalance @ 800kHz max. 300 pF/100m
Operating voltage max. 300 V
REACTION TO FIRE CLASSIFICATION
CPR Euroclass: Cca s1d1a1
CPR UKCA Class: Cca s1d1a1
APPLIANCE
Cable for use in bus systems (EIB - European Installaton Bus) and as ICA cable in power installations. Laying in/on plaster, even in moist and wet rooms. Not approved for power and underground installation.
PACKING
100 m / coil